Sign In | Join Free | My himfr.com
Home > CT PT Analyzer >

Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG

    Buy cheap Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG from wholesalers
     
    Buy cheap Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG from wholesalers
    • Buy cheap Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG from wholesalers
    • Buy cheap Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG from wholesalers
    • Buy cheap Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG from wholesalers
    • Buy cheap Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG from wholesalers

    Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG

    Ask Lasest Price
    Brand Name : GFUVE
    Model Number : GF1061PT
    Certification : ISO9001:2015, EPRI
    Price : 30000USD/set
    Payment Terms : L/C, D/A, D/P, T/T, Western Union, MoneyGram
    Supply Ability : 200sets/month
    Delivery Time : 5-8days
    • Product Details
    • Company Profile

    Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG

    GF1061PT with Polarity, ratio & phase error Portable Voltage transformer PT Analyzer

    GF1061PT is the first portable device (4.8 kg) which offers highly accurate voltage transformer tests. This allows to use GF1061PT not only for electrical performance checks, but also for class verification and calibration. It performs quick tests of all kinds of inductive voltage transformers (VTs or PTs) and capacitive voltage transformers (CVTs) for both protection and metering purposes. Its lightweight design makes it ideal for on-site tests and calibration tasks in power system grids.

    Description

    As a manufacturer or testing lab you can use GF1061PT in your production facilities and test/development labs. it can finish the measurements (M) and protection (P) class PT. Adopt 7 inch touch TFT color LCD, self-equipped mini type printer supporting field printing; supporting to use USB flash disk to dump data. The GF1061PT portable PT tester is the most complete and easy-to-use testing system for PTs according to IEEE and IEC standards.

    Features

    • Tests of various types of measurement and protection VTs and CVTs
    • The use of advanced power technology, the test knee point reaches up to 80kV
    • No external other auxiliary equipment, stand-alone to complete all test items
    • Tests such as ratio, phase, polarity, capacitive ratio
    • PT test, easy to test, all the tests are using the same wire connection except the load test
    • It carries with thermal printer, printing test results on site
    • Parameters such as knee point current and voltage
    • Parameters such as 10% error curve, 5% error curve
    • With battery, working one week.
    • The device can store 10000 groups of test data which would not be lost if the device is power off.
    • The data can be displayed and analyzed after the test, or transferred to PC through USB disk and produce a Word or PDF file report
    • Portability: weight 4.8kg, the best light pt analyzer

    FUNCTION

    I. Voltage Transformer (PT)
    1. Excitation characteristic test
    2. Transformation ratio test
    3. Polarity
    4. Ratio error, phase error
    5. Degauss
    6. Calculation of knee point value
    7. Actual secondary load test (burden test)
    8. Resistance test

    Parameters

    Electrical parameters
    Accuracy0.02%
    Power supplyAC 220V±10% or AC 120V±10%, 50/60Hz or Battery
    Output voltage0-100Vrms
    Output current0-5Arms (20A peak-value)
    Output power0-400 VA (1500 VApeak)
    Automatic frequency variation range0.1-60Hz
    Equivalent excitation voltage≤5000V/50KV
    Accuracy≤0.5%
    Secondary winding DC resistance measurementRange0.1-1000Ω
    Accuracy≤0.05%
    Secondary actual load measurementRange5VA-1000VA
    Accuracy≤0.5%±0.1VA
    PT phase error measurementAccuracy±1min (typical) / 3 min (guaranteed)
    Resolution0.1min
    PT ratio error measurementRange1-15000
    Accuracy≤0.05%
    LCD display7' inch TFT touch color LCD
    Communication portUSB port
    PrinterYes, Thermal printer
    Standards
    Reference standardsGB1207-2006, GB1208-2006, GB16847-1997
    IEC60044-1, IEC60044-6, IEC61869, ANSI/IEEE C57.13
    Safety standardsGB 4793.1-2007
    EMCEMC standard 89/336/EEC
    FCC Subpart B of Part 15 Class A
    IEC 1000-4-2/3/4/6
    Mechanical parameters
    Overall dimension (L x W x H) (mm)280 x 250 x 160
    Weight (kg)≤4.8
    Environmental conditions
    Relative humidityRelative humidity 5%-95% not condensing
    Operating temperature-10°C to +50°C
    Storage temperature-20°C to +70°C
    Altitude≤1000m

    Photo


    Quality Portable Voltage PT Power Transformer Testing Equipment With Polarity 4.8KG for sale
    Inquiry Cart 0
    Send your message to this supplier
     
    *From:
    *To: Beijing GFUVE Instrument Transformer Manufacturer Co.,Ltd.
    *Subject:
    *Message:
    Characters Remaining: (0/3000)