    2nd Harmonic Electricity Meter Calibrator 12A Automated Analyzer

    Ask Lasest Price
    Brand Name : GFUVE
    Model Number : GF312D1
    Price :
    Payment Terms : T/T, Western Union, MoneyGram
    Supply Ability : 1500SETS/MONTH
    Delivery Time : 1-2WEEKS
    • Product Details
    • Company Profile

    2nd Harmonic Electricity Meter Calibrator 12A Automated Analyzer

    FEATURES

    • Analyze and display content of harmonic of U and I.
    • Measure 2-64 harmonic of U, I.
    • Store and display measured data.
    • Optional 5A, 20A, 100A, 500A, 1000A, 2000A, 3000A current clamp.
    • Measure CT variable ratio.
    • Measure the ratio or lag-angle of low-voltage transformer.
    • Adopt 32 bit ARM processor, multi-channel 16 bit precision A/D convertor, high resolution TFT color LCD.
    • Inner equipped with 0.01% wide-range current transformer and can be equipped with various type current clamps, wide range of measurement and high veracity.
    • Low consumption circuit design, high energy Lithium battery supply, intellectual power management software, which enables the instrument continuously working up to 10 hours

    TECHNICAL PARAMETERS

    1.Electrical parameters 
    Accuracy class0.05%, 0.1%
    Display6”TFT (640×480)
    Power supply220V±10%, 50/60Hz
    Li-polymer battery (size (mm): 110x51x16, nominal output voltage: 7.2V, capacity: 5000mAh)
    Power line supply (U1, UN), 85V-265V 50/60Hz
    Communication portRS232
    Test voltage
    RangePhase to Netural 0-480V (Phase to Phase 0-830V)
    Error±0.05% (30V-480V)
    ±0.1% (5V-30V)
    Voltage measurement temperature drift< 8 x 10 E-6/K
    Voltage measurement relative humidity drift< 8 x 10 E-6/RH
    Voltage measurement stability< 50 x10 E-6
    Voltage measurement long term stability< 80 x 10 E-6/Year
    Harmonic2nd-64st
    Test current
    Range (direct connection)0-12A
    Error (direct connection)±0.05% (100mA-12A)
    ±0.1% (10mA-100mA)
    Range (clamp CT)10mA-120A

    Power & Energy measure error
    Active power (direct connection)±0.05% (0.1A-12A)
    ±0.1% (0.01A-0.1A)
    Reactive power (direct connection)±0.1% (0.1A-12A)
    Energy measure error
    Active energy (direct connection)±0.05% (0.1A-12A)
    ±0.1% (0.01A-0.1A)
    Reactive energy (direct connection)±0.1% (0.1A-12A)
    Power/energy measurement temperature drift< 15 x 10 E-6/K
    Power/energy measurement relative humidity drift< 12 x 10 E-6/RH@ 10mA-120A
    Power/energy measurement stability< 100 x10 E-6
    Power/energy measurement long term stability< 160 x 10 E-6/Year
    Error display5 digits with minimum three decimal places XX.XXX%
    Phase angle
    Range0°-360°
    Resolution0.01o
    Error±0.05°
    Frequency
    Range40-70Hz
    Resolution0.001Hz
    Error0.002Hz
    Pulse input
    Input channel2
    Input level5-24V
    Input frequencyMax. 2MHz
    Pulse output
    Energy constant180000imp/kWh, 1800imp/kWh, 180imp/kWh
    Pulse ratio1:1
    Output level5V
    Pulse frequencyStandard 400Hz-1KHz, customized max 10KHz

    Function
    Vector diagramYes
    WaveformYes
    Energy accumulationYes
    Communication with PCYes
    Overload protectionYes
    2.Cable and Accessories
    Test CableVoltage test cable 1SET Cable Length:2m (R,Y,B,Black)
    Current test calbe 1SET Cable Length:2m (R,Y,B,Black)
    PlugPin type 1SET (4black,2Red,2Yellow,2Green)
    'U' type 1SET (4black,2Red,2Yellow,2Green)
    'Ω' type 1SET (4black,2Red,2Yellow,2Green)
    Crocodile type 1SET (1Black,1Red,1Yellow,1Green)
    Accessories BagYes
    3.Mechanical parameters
    Instrument dimensions (W×H×D) (mm)245×162×60
    Instrument Weight (kg)1.8
    Carry case dimensions (W×H×D) (mm)450×320×185
    Carry case (kg)10.6
    4.Environmental conditions
    Ambient temperature-10°C to 55°C
    Relative humidity15%-95%
    Environmental protection levelIP51
    5.Standard
    lsolation protectionIEC 61010-1:2001
    Energy measurementIEC 60736
    Reference standardIEC 62052-11
    IEC62053-21
    IEC62053-22 & IEC62053-23
    IEC61010-1:2001
    6.Calibration and maintenance
    Warranty5 years
    CalibrationLifelong free calibration service